Outfitting
- Double doors, 6’ x 6’-8” x 1 3/4”; 18 gauge galvanized steel; insulated; tamper-proof hinges; deadbolt lock; adjustable mechanical door hold-open arm; door stop and holder; rain guard
- Extruded aluminum threshold with integral neoprene seal
- Two 12.5-gauge screened aluminum vents; minimum 7” x 18”
- Post-tensioned roof and floor (20' and 24' roof widths, prestressed for 30', 40', & 50’ roof widths for Easi-Span Building Models)
- 5,000 psi steel-reinforced concrete
- We can work with you to customize outfitting to meet your specific needs.
Capacities and Capabilities
- Roof load capacity: 60 psf standard; higher loadings available
- Wind load: 165 mph standard; higher loadings available
- Rated seismic Design Category ‘D’ (heavier available)
- Floor load: 250 psf standard; additional capacities available
- Meets IBC requirements
- Bullet tested to UL 752, Level 5 (7.62 x 51 M80 projectile fired at 16 feet)
Top